Etaline PumpDrive,Close-coupled in-line circulator pump

Design
Close-coupled in-line circulator pump with motor-mounted variable speed system; pump shaft and motor shaft are rigidly coupled.              
Applications
Hot water heating systems, cooling circuits, air-conditioning systems, water and service water supply systems, industrial recirculation systems.

Overview of technical data

Type of impeller                                                                         Closed / Radial                    
Type of installation                                                                         In- line                    
Maximum drive rating                                                                         45                         kW                    
Impeller material (EN standard)                                                                         1. 4408;CC480KK-GS;EN-GJL-250                    
Type of bearing                                                                         Ball bearings                    
Drive frequency                                                                         50 Hz / 60 Hz                    
Maximum flow rate                                                                         700                         m³/h                    
Maximum discharge-side pressure                                                                         16                         bar                    
Suitable for drinking water                                                                         Yes                    
Casing material (EN standard)                                                                         EN- GJL-250                    
Casing material                                                                         Cast iron                    
Integrated control system                                                                         Yes                    
Suction characteristics                                                                         Non- priming                    
Drive voltage                                                                         Low voltage                    
eClass assignment                                                                         36410101                    
Pump set location                                                                         Dry installed                    
Max. permissible fluid temperature                                                                         110                         °C                    
UNSPSC classification                                                                         4515150300                    
Main applications                                                                         Industry and process engineering; Building services;Water                    
Type of installation                                                                         Stationary                    
Type of casing                                                                         Volute casing                    
Type of connection                                                                         Flange                    
Type of lubrication                                                                         Grease lubrication                    
Type of drive                                                                         Electric motor                    
Installation position                                                                         Horizontal or vertical                    
Shaft material (EN standard)                                                                         1. 4571;C45+N                    
Shaft seal type                                                                         Mechanical seal                    
Drive                                                                         Electric motor                    
Maximum head                                                                         95, 00                         m                    
Maximum rated pressure (discharge)                                                                         PN 16                    
Nozzle position                                                                         In- line                    
Connection to power supply                                                                         400 V, 3~